For the closed cooling tower, the fan, spray pump is the key components of the operation of the entire equipment, for the maintenance of these components, we must strictly abide by the necessary management practices, the following we combined cooling tower, for example, Detailed description of the relevant management practices:
1, the fan: the fan must check the fan motor power cut off. Sometimes due to automatic operation and other reasons, the fan will suddenly start a very dangerous. But also in the shutdown when the power to cut off to restore the power supply when the fan suddenly started very dangerous.
⑴, to confirm whether the leaves are deformed, damaged, or with or without dust, dirt and other attachments. In addition, make sure that the gap between the inner surface of the tower and the blade is uniform on the circumference. In addition to any exception.
⑵, fan with a motor to start a frequent stop will produce a failure. Should pay attention to the operation method, so that the number of starts controlled at 4 times / hour or less.
2, spray pump, circulating pump: check the pump, be sure to cut off the power pump. Sometimes due to automatic operation and other reasons, the pump suddenly start very dangerous.
⑴, pressure, flow, current, vibration, noise and so on when the difference is usually a precursor to the fault, it is very important to deal with. So please do the running diary.
⑵, vibration, please check the installation of the pipe or the basic bolt is loose. Sometimes caused by circulating water vibration, in the piping should be considered to install flexible joints, pressure vibration or absorption device.
⑶, if the pump outlet valve closed for a long time running, will make the internal burn out, should pay full attention.
⑷, frequent start, stop will soon burn the motor. Please follow the following benchmarks to control the number of starts. Motor power start number 7.5kw or less 6 times / hour or less 11kw or less 4 times / hour or less
⑸, long-term stop running or maintenance, the winter when the pump stops when the internal water if the ice, the pump will freeze. The pump must be insulated or the internal water drained.
For more information, please visit our website: www.coolingtowerfiller.com, or contact us with E-mail, our E-mail address is rask@coolingtowerfiller.com, you can also chat us straightly on whatsapp: 008618330029204
订阅:
博文评论 (Atom)
closed type cooling tower
new 1000*1300mm spindle cooling tower pvc fill pack Cooling Tower has roots inside the cooling tower industry that span again greater t...
-
new type Marley cooling tower pvc filler For the reason that cylinder chamber is open to the discharge manifold, no refrigerant gasoline c...
-
750 x 2000mm Kuken cooling tower pp filling Cooling towers are heat rejection devices. They are integral to many refrigeration programs in...
没有评论:
发表评论