Cooling tower filler is the core equipment of the circulating water system, the circulating water equipment management situation, whether it is from the number of equipment, maintenance workload, power consumption and other aspects of terms, the cooling tower fans are occupying a large proportion. The number of fans accounted for 57% of the total plant equipment, maintenance work accounted for 60% of the total, electricity consumption accounted for 22% of the total. How to save energy and reduce the labor force in the case of ** long-term operation of the device, the following simply talk about the measures:
1, cross-flow cooling tower should control the top of the grid filler to the lower edge of the suction fan is equal to or greater than the fan diameter of 0.2 times.
2, countercurrent cooling tower grid filler top to the inlet between the air duct to reach the height of the contract should meet the following requirements:
1) When the top cover of the tower is flat, the angle of the air flow from the top of the mesh packing shall be less than 90 °. When the guide ring (umbrella) is provided under the flat roof cover, The top of the air flow contraction section of the vertex angle can be used 90 ° ~ 110 °.
2) When the top of the tower from the collector above the shrinkage type, the contraction of the cover of the top angle should be used 90 ° ~ 110 °.
3, cross-flow cooling tower of the water grid packing from the top to the bottom should have a vertical axis of the tower to the contraction angle. The shrinkage angle of the drip grill packing is preferably 9 ° to 11 °; the shrinkage angle of the thin film-type grill grid packing should be 5 ° ~ 6 °.
4, the two sides into the wind countercurrent cooling tower should be set in the middle of the wind partition, the upper edge of the partition from the grid packing support beam at the end of 200 ~ 300MM, the lower edge of the tower into the pool below the water.
5, cross-flow cooling tower should be set to prevent the air from the bottom of the grid filler to the surface of the short-circuit flow measures.
For more information, please visit our website: www.coolingtowerfiller.com, or contact us with E-mail, our E-mail address is rask@coolingtowerfiller.com, you can also chat us straightly on whatsapp: 008618330029204